Input: | |
Voltage Range | |
– Low Line Transfer | 180VAC/160VAC/140VAC/120VAC ± 5% |
(Based on load percentage) | |
– Low Line Comeback | 195VAC/175VAC/155VAC/135VAC ± 5% |
High Line Transfer | 300 VAC ± 5% |
High Line Comeback | 290 VAC ± 5% |
– Frequency Range | 40Hz ~ 70 Hz |
Phase | Single Phase with ground |
Power Factor | ≥ 0.99 @ nominal voltage (input voltage) |
Output: | |
Output Voltage | 208/220/230/240VAC |
Output Power Factor | 0.8 |
AC Voltage Regulation | ±1% (Battery Mode) |
Frequency Range | 47-53 Hz or 57 – 63 Hz (Synchronized Range) |
Frequency Range (Battery Mode) | 50 Hz ± 0.5% or 60Hz ±0.5% |
Overload: | |
– Ambient Temp. <35°C | |
– 105%~110% | Shuts down after 10 minutes at battery mode or transfer to bypass when the utility is normal |
– 110%~130% | Shuts down after 1 minute at battery mode or transfer to bypass when the utility is normal |
– ≥ 130% | Shuts down after 3 seconds at battery mode or transfer to bypass when the utility is normal |
Battery: | |
Battery Type | 12 V / 9 AH |
Battery Numbers | 6 |
Recharge Time | 4 hours recover to 90% capacity (typical) |
Charging Voltage | 82.1 VDC ± 1% |