Input | |
– Capacity | 3000 VA / 2700 W |
– Low Line Transfer | 180VAC/160VAC/140VAC/120VAC ± 5% |
(Based on load percentage) | |
– Low Line Comeback | 195VAC/175VAC/155VAC/135VAC ± 5% |
– High Line Transfer | 300 VAC ± 5% |
– High Line Comeback | 290 VAC ± 5% |
– Frequency Range | 40Hz ~ 70 Hz |
– Phase | Single Phase with ground |
– Power Factor | ≥ 0.99 @ nominal voltage (input voltage) |
Output | |
– Output Voltage | 208/220/230/240VAC |
– Output Power Factor | 0.9 |
– AC Voltage Regulation | ±1% (Battery Mode) |
– Frequency Range | 47-53 Hz or 57 – 63 Hz (Synchronized Range) |
– Frequency Range (Battery Mode) | 50 Hz ± 0.5% or 60Hz ±0.5% |
– Harmonic Distortion | ≤ 3% THD (linear load); ≤ 6% THD (non-linear load) |
Overload | |
– Ambient Temp. <35°C | |
– 105%~110% | Shuts down after 10 minutes at battery mode or transfer to bypass when the utility is normal |
– 110%~130% | Shuts down after 1 minute at battery mode or transfer to bypass when the utility is normal |
– ≥ 130% | Shuts down after 3 seconds at battery mode or transfer to bypass when the utility is normal |
– Current Crest Ratio | Current Crest Ratio |
– Harmonic Distortion | ≤ 3% THD (linear load); ≤ 6% THD (non-linear load) |
Transfer Time | |
– AC Mode to Batt. Mode | Zero |
– Inverter to Bypass | 4 ms (Typical) |
– Waveform (Battery Mode) | Pure Sinewave |
Efficiency | |
– AC Mode | 90% |
– Battery Mode | 88% |
Battery | |
– Battery Type | 12 V / 9 AH |
– Battery Numbers | 6 |
– Recharge Time | 4 hours recover to 90% capacity (typical) |
– Charging Voltage | 82.1 VDC ± 1% |
Physical | |
– Dimensions (D × W × H, mm) | 421 × 190 × 318 |
– Net Weight | 27.6 kgs |
Environment | |
– Operation Humidity | 20–90% RH @ 0–40°C (non-condensing) |
– Noise Level | < 45dBA @ 1 Meter |
Management | |
– Smart RS-232 or USB | Supports Windows® 2000/2003/XP/Vista/2008/7, Linux, Unix and MAC |
– Optional SNMP | Power management from SNMP manager and web browser |